- Fire Emergency Lighting and Evacuation Indication System
- Fire Power Module
- Electrical Fire Monitoring System
- Smart Electricity Monitoring System
- Emergency Power Supply
- Power Monitoring System for Fire Equipment
- Fire Door Monitoring System
- Intelligent Lighting Control System
- Intelligent Residual Pressure Monitoring System
- Intelligent CO Monitoring System
- Graphic Display Device
- Independent Smoke Detector
- Fire-Fighting Electrical Control Device
PW-B-01 (08G) detector
Rated working voltage Ue (V) |
AC220V |
Product features |
Detection of 1-circuit leakage current, 4-circuit temperature, three-phase voltage, three-phase current, trip output |
Warning and alarm threshold of residual current |
100 mA~900 mA (settable), with a step length of 1 mA |
Temperature warning and direct report |
30°C~200°C (settable),with a step length of 1 mA |
Accuracy of voltage/current value |
<=3% |
Alarm parameter |
Undervoltage, overvoltage, default phase, overcurrent, overtemperature, over-residual current |
Alarm time |
<5s |
Protective action |
<=0.5s |
Installation mode |
Rail-mounted |
Display method |
LCD display |
Communication mode |
GPRS/NB-IoT |
Alarm sound |
>=70dB |
Ambient temperature |
-25°C~+50°C |
Altitude |
<=3000m |
Focus News
Mid-Autumn Festival and National Day, safe companionship
Sign the promise and energize

HOTLINE
Licheng District, Jinan City, Zhihuiling Intelligent Manufacturing Technology City
版权信息