PW-D Centrally-Connected Power Supply
Model |
PW-D-0.3/0.5KVA |
PW-D-0.5/1/2/3/5~12KVA |
|
Main power input |
Number of phases |
Single-phase |
Three-phase or single-phase |
Voltage |
AC 220V(-15%~ +10%) |
AC 380V or AC 220V(-15%~+10%) |
|
Frequency |
50Hz |
||
Emergency output |
Voltage |
DC 36V |
AC 220V/DC 36V |
Overload capacity |
Work normally at ≤120% rated current |
||
Stop output 1 s after normal output at >120% rated current |
|||
Battery |
Type |
Sealed and maintenance-free battery |
|
Standby time |
90 min or according to user requirements |
||
Charging time |
<20h |
||
Communication mode |
Uplink communication CAN bus/downlink communication P-BUS |
||
Output circuit |
1-8 circuits |
||
Conversion time |
Non-disruptive switching |
≤0.25s |
|
Protection |
Overload protection, output short circuit protection, battery polarity reversal protection, battery undervoltage protection |
||
Alarm |
Battery undervoltage, battery connection failure, charger failure, continuous overload |
||
Ambient temperature |
-25°C~ +50°C |
||
Ambient humidity |
≤90% RH (non-condensing) |
||
Altitude |
≤3000 m, can be derated above 3000 m |
||
Noise |
≤ 55 dB at main power output, no noise during emergency output |