PW-D-QQKVA series EPS products
Technical parameters of product |
||||
Input |
Voltage (V) |
Single-phase 220V (-15%~+10%) or three-phase 380V (-15%~+10%) | ||
Frequency (Hz) |
50Hz±5% |
|||
Output |
Voltage (V) |
EmergencyAC220C±0.5% ,consistent with the mains voltage in normal state |
Frequency (Hz) |
Emergency50Hz±0.5% ,consistent with the mains voltage in normal state |
Switch time |
<=3s |
Display |
LCD display |
|
Relative humidity |
0-90% |
Ambient temperature |
-25°C~ + 50°C |
|
Altitude |
<=3000m |
Insulation strength |
AC1500/50Hz , lmin |
|
Insulation resistance |
>=50MQ |
Adaptive load |
Mainly used for various loads such as lighting | |
Battery |
Sealed and maintenance-free battery |
Noise |
Mute when there is mains supply, V55 dB in emergency state (<65 dB when it’s above 80 kVA) |
|
Waveform |
Consistent with the mains voltage in normal state, and sine wave in emergency state |
|||
Duration of emergency power supply |
90 min as standard or manufactured according to design requirements |
|||
Overload capacity |
Works normally when ≤120%, and automatically shuts down after 10 s when >150% |
|||
Effectiveness |
More than 90% in emergency, and tends to 100% in normal state |
|||
protection |
Short circuit protection, overcurrent protection, undervoltage protection |